When connecting aluminum service conductors to a breaker panel, do I need to use antioxidant?
You are currently browsing comments. If you would like to return to the full story, you can read the full entry here: “When connecting aluminum service conductors to a breaker panel, do I need to use antioxidant?”.
Filed under: Alternative Medicine
Like this post? Subscribe to my RSS feed and get loads more!

Aluminum to Aluminum they say you do not need an inhibitor. I have still aways used it as has every electrical contractor I have worked for for 30 years. Utility companies use it on all meter bases as well. The oxidation can still be persistent so I suggest you use it and torque them to the manufactures labeling.
So many people over tighten the conductors and this is a major problem because aluminum is very soft it does have a torque guideline for each conductor size as well as the lug it is attached to.
Electrical Contractor |><|
No you do not have to use any type compound on it.